GÜRAL ELEKTRİK
Indoor Switch-disconnector
Technical ratings and configuration options for this product family are listed below where available. Contact our technical team to select the right configuration for your project.
TECHNICAL INFORMATION
Technical specifications
Ratings are taken from the available product information; final values must be confirmed for the specific type and configuration.
| Technical parameter | Value |
|---|---|
| Rated voltage | 12–36 kV |
| Rated current | Up to 630 A |
| Peak withstand current | 52 kA peak |
| Installation environment | Indoor installation |
| Class | Class E3 general-purpose switch |
| Rated mainly active load breaking current | 630 A – 100 opening and closing operations |
| Short-time withstand current / duration | 20 kA / 1 s |
| Short-circuit making current (peak) | 42 kA |
| Applicable standards | IEC 62271-1; IEC 62271-102; IEC 62271-103; TS EN 62271-1; TS EN 62271-102; TS EN 62271-103 |
Technical drawings and documents
Güral Elektrik General Catalogue
View PDF ↗Download PDF ↓See the relevant catalogue for product options and technical documentation.